zrwnn

This mode is intended for a simple natural ventilation system, possibly simulating simple occupant control, where openings are controlled from a single zone's resultant temperature. This mode requires the following parameters.

 

Parameter

Description

Zone

The zone name whose resultant temperature will control the aperture.

Lower limit

The aperture will be closed if the controlling zone resultant temperature is below this value.

Upper limit

The aperture will be fully open if the controlling zone resultant temperature is above this value.

Upper wind speed

The aperture will start to close when the wind speed exceeds this value. The aperture will be fully closed at 0.5m/s above this value.

 

For example, the automatic control function zrwnn could have the parameters set as follows:

This would define the following strategy for aperture opening. As the resultant temperature in zone 5 rose above 22C the aperture would start to open. The aperture would be fully open at 24C and remain fully open at all temperatures above 24C. The wind speed will also start to shut the aperture as it increases above 5m/s and be fully closed at 5.5m/s. For a full description of how final aperture opening values are calculated please see the section: Aperture Type Functions.

 