Setting Up a Fancoil System

 

 

Exercise and Notes

 

  1. In this example 90% of the air will come into contact with the cooling coil. You should set the bypass factor to 0.1.

  2. The terminal fan SFP has been specified as 0.3 W per l/s. The notional building will also use a fan SFP of 0.3 W per l/s.

  3. The extract fan has been modelled with an SFP of 0.6 W per l/s and the fresh air fan will produce 1.2 W per l/s. This is equivalent to the notional building which will have an SFP in the central AHU of 1.8 W per l/s.

  4. The associated zones will benefit from demand control ventilation as a function of occupancy density where air flow will be regulated by fan speed as opposed to dampers.

  1. Monitoring for out-of-range values = True.

 

Next