zrest

This mode is intended for a heating or cooling system where the capacity is controlled from a single zone's resultant temperature. This mode requires the following parameters.

 

Parameter

Description

Zone

The zone number whose dry bulb temperature will control the heating or cooling capacity. If you enter 0 for this value, the capacity will be controlled on the temperature of the zone that this internal condition is applied to.

Off

For heating emitters, The heating will be off if the controlling resultant temperature is above this value.

For cooling emitters, the cooling will be off if the controlling zone resultant temperature is below this value.

Max

For heating emitters, the heating capacity will be at its maximum if the controlling zone resultant  temperature is below this value.

For cooling emitters, the cooling capacity will be at its maximum if the controlling zone resultant  temperature is above this value.

 

For example, 'Zrest,5,21,19' would define the following strategy for heating. As the resultant temperature in zone 5 went below 21C then heating would be available, if needed. The heating capacity would be at its maximum value when the temperature was at or below 19C.

 

 'Zrest,5,23,25' would define the following strategy for cooling. As the resultant temperature in zone 5 went above 23C then cooling would be available, if needed. The cooling capacity would be at its maximum value when the temperature was at or above 25C.

 