Lighting Gain Functions

Automatic control functions exist for the lighting which will allow you to control how much lighting gain there will be in a zone based on the calculated illuminance levels at each hour. A lighting function can reference the applied zone, or it can use another zone in the model as the control. To use a lighting function you will need to have calculated a daylight factor in the zone for which the lighting function will be referencing (the 'control zone'). The daylight factor is defined as the average diffuse illuminance on the working plane within the zone as a percentage of the diffuse illuminance on a horizontal plane outside of the building. Daylight factors can be calculated using the daylight facility which has been built into the 3D Modeller (see the Tas Daylight user-guide for more details), or you can use the Daylight Factor Calculator in the Utilities folder to calculate daylight factors using an approach based on the simplified BRE method.

 

Three different control types are available, they are called 'Manual Control', 'Photocell Control', and 'No Control'. There are two calculation methods to choose from, you can select either 'Gain Method' or 'Efficacy Method'. These will be described below, and on the lighting pages to follow.

 

On the internal conditions Gains table, click on 'Lighting Gain' and then set the Type value to 'Function' on the Profile dialog. This will open the Lighting Control Function window, which is where you will set the control type, calculation method, and lighting parameters. After selecting a control type and calculation method, the relevant mnemonic code will be visible in the function description, which can be found below the Parameters section.

 

So each lighting function will have its own mnemonic code, depending on control type and calculation method - there are five function definitions to choose from. The codes for the lighting functions are given below (the function definition is described in a new topic, click on the link to go to that topic):

When manual control is paired with the gain method, the lighting gain in the zone will be determined by the mlclg function definition. When manual control is paired with the efficacy method, the mlcle function call will be made instead. So if the fifth letter in the mnemonic is a 'g' then it will be using the gain calculation method, and if the last letter is an 'e' then it will be using the efficacy method. To use the plclg function, you should select the photocell control type and set the calculation method to 'Gain Method'. You can use plcle by using photocell control and choosing the efficacy method. Finally, the nlcle function will be used when you select efficacy and then set the control type to 'No Control'. This information has been summarised in the table below:

Table of Function Mnemonics

 

Gain Method

Efficacy Method

Manual Control

mlclg

mlcle

Photocell Control

plclg

plcle

No Control

No available function

nlcle

 

The Lighting Control Function dialog will give you the chance to set values for various parameters, for example you will be able to set the minimum room illuminance that will be used to determine when the lighting gain is at its maximum. The two main sections on the dialog are described as 1. Control Logic, and 2. Parameters. The SI (metric) measurement units are given in the following table.

Table of SI (Metric) Measurement Units

Lighting Parameter

Unit of Measurement

Illuminance

lx

Lighting gain

W/m^2

Efficiency

W/m^2.100lx

Area cut-off

m^2

Efficacy

lm/W

Parasitic power

W/m^2

 

For the US Customary (I-P) measurement system, illuminance will be given in foot-candles (fc), gains will be given in W/ft^2, and efficiencies will be given in W/ft^2/100fc. To change between measurement systems, click on the Settings button on the Tas Manager and then click on the Measurement System down-arrow on the Localisation tab.

mlclg